  • Megger BM80/2 (50V-1000V) Insulation Tester

Megger BM80/2 (50V-1000V) Insulation Tester

Megger

£35.00 per week


Call 01925 720 001

Contact Us

The Megger® BM80/2 Series are multi-voltage insulation and continuity testers offering advanced performance, specification and features, and simplicity of use. They have insulation test voltages from 50 V to 1000 V d.c., (500 V max. on BM81/2.) The comprehensive specification is achieved using the latest electronic design and technology.

The analogue/digital LCD incorporates the benefits of electronic arc analogue indication with unambiguous digital readings. The analogue scale helps to make rapid identification of insulation condition, and to monitor variable readings, and is complemented by the precision and simplicity of a digital display. All 3 instruments in the range are identical except that the BM81/2 has a maximum test voltage of 500 V and the BM82/2 has no continuity range.

In compliance with BS 7671, IEC 364, HD 384 and VDE 0413 Part 1 and 4, the 250 V, 500 V and 1000 V insulation ranges have a 1 mA test current at the minimum pass values specified. The BM80/2 and BM81/2 continuity ranges have a short circuit test current of approximately 205 mA in order to comply with the requirements of these documents. Also on the continuity ranges, is the facility to null the resistance of the test leads.

This enables direct readings of low resistance to be taken. A continuity buzzer is included on the second continuity range.

In addition to the insulation and continuity ranges, the BM80/2 series has a resistance range which measures up to 100 kΩ on the digital scale and up to 10 MΩ on the analogue scale. Due to the low test voltage and current of this range, it can be used to test circuits with sensitive equipment connected, without causing damage.

Two voltage ranges measure up to 50,0 V and 600 V a.c. or d.c. respectively, and indicate the presence of negative d.c. A voltage warning is provided in these models, alerting the user to the presence of external voltage greater than 25 V, by displaying the voltage level, even when measuring on insulation and continuity ranges. The voltage range will indicate if capacitive charge remains after a test, and will monitor the automatic discharge. On all models testing is inhibited if 55 V is detected.

Hands free operation is offered as standard on all ranges except the insulation ranges. Locking and non-locking test buttons are provided with each instrument for user selection. Use of the non-locking button is recommended to prevent accidental mis-use and injury, and in cases where continuous operation of an insulation test is required the locking button can be fitted. Alternatively the optional accessory Switched Test Probe SP1 can be used enabling remote operation of the test button from the negative test probe.

The BM80/2 series is rugged, and therefore suited to tool bag treatment, as well as having an IP54 environmental protection rating which ensures product reliability in wet and dusty conditions. Exceptional battery life is provided by six cells housed in separate battery compartment. The instruments are designed to IEC 1010-1, VDE0411 and BS4743 safety standards.

Features

  • Fully complies with the requirements of BS 7671, HD 384 and IEC 364
  • Multiple insulation test voltages from 50 V to 1000 V d.c. (according to model)
  • Remote control switched probe option
  • Optional RS232 port
  • Optional current clamp accessory
  • Waterproof and dustproof to IP54
Datasheet PDF